The VISTA-128FBP provides the ultimate protection of life and property. This UL Listed commercial fire and burglary control panel supports up to eight partitions and up to 128 zones/points using hardwired, wireless and V-Plex® addressable technologies.
- Eight hardwired zones standard, expandable to 120 V-Plex addressable points/zones or 128 wireless points/zones
- Can control eight separate areas independently (8 partitions)
- Supports wireless fire and burglary devices
- Stores up to 512 events
- Accommodates 150 user codes and up to 250 access card holders using VISTAKEY®
- Supports V-Plex addressable VISTAKEY access control (1 to 8 doors)
- Two on-board notification (bell) circuits delivering 2.3A @ 12V
- Automatic smoke detector sensitivity maintenance testing
- Four-wire smoke reset using onboard J2 output trigger
- Supports Dynamic Signaling for AlarmNet Communicators
- Supports Internet and GSM alarm reporting*
- Supports graphical user interfaces for burglary use
- Supports 6160CR-2 multi-LED fire keypad
- Listed to UL864 9th Edition
- Upload/download via Ethernet when used with Ethernet devices.
- Carbon monoxide (CO) zone support
Electrical
- Primary power: 18VAC @ 72VA Honeywell No. 1451
- Control panel quiescent current draw: 300mA
- Backup battery: 12VDC, 12AH min to 34.4AH max Lead acid battery (gel type)
- Alarm power: 12VDC, 1.7A max for each notification (bell) circuit output Total 2.3A 12V
- Aux. standby pwr: 12VDC, 1A max Total power: 2.3A at 12VDC
- Standby time: 24 hours with 1A standby load using 34.4AH battery
- Fusing: Battery input, aux. and notification (bell) circuit outputs are protected using PTC circuit protectors. All outputs are power limited. Optional 24-volt kit